Fonctions de surveillance | Échec de phase | 500ms |
Séquence de phase | — | |
Protection asymétrique réglable / fixe | ± (5% => 20%)/ OFF | |
3% x Un ≈ 12 VAC | ||
0.1=>10s | ||
Protection de tension réglable | + (5% => 20%)/OFF | |
-(5% => 20%)/OFF | ||
6 VAC | ||
0.1=>10s for off delay operation |
Général | Max. 250ms |
Relay | |
Contacts auxiliaires | 1 C/O (SPDT) |
10A/250V; 1250 VA | |
5A/30VDC; 150W | |
≥ 107 operations | |
5×104 (5A@250VAC) 1×105 (5A@30VDC) | |
Tension d’alimentation | — |
380-480VAC ±25% from L1-L3 | |
Général | 50-60Hz |
— | |
Conditions ambiantes | -20 to +60 °C |
-40 to +75 °C | |
Max.95% (no condensation) | |
Général | 50-60Hz |
IP20 | |
Consommation d’énergie | — |
<4VA |