| Fonctions de surveillance | Échec de phase | 500ms |
| Séquence de phase | — | |
| Protection asymétrique réglable / fixe | ± (5% => 20%)/ OFF | |
| 3% x Un ≈ 12 VAC | ||
| 0.1=>10s | ||
| Protection de tension réglable | + (5% => 20%)/OFF | |
| -(5% => 20%)/OFF | ||
| 6 VAC | ||
| 0.1=>10s for off delay operation |
| Général | Max. 250ms |
| Relay | |
| Contacts auxiliaires | 1 C/O (SPDT) |
| 10A/250V; 1250 VA | |
| 5A/30VDC; 150W | |
| ≥ 107 operations | |
| 5×104 (5A@250VAC) 1×105 (5A@30VDC) | |
| Tension d’alimentation | — |
| 380-480VAC ±25% from L1-L3 | |
| Général | 50-60Hz |
| — | |
| Conditions ambiantes | -20 to +60 °C |
| -40 to +75 °C | |
| Max.95% (no condensation) | |
| Général | 50-60Hz |
| IP20 | |
| Consommation d’énergie | — |
| <4VA |